Fiber is simpler than copper in one way: it is immune to electrical noise and does not care about grounding. It is less forgiving in another: a mismatched optic, polish, or polarity produces a dead link with no negotiation to explain it.

Two fibers

Type Core Distance Use
Multimode OM3 50 µm 300 m at 10G Building backbone
Multimode OM4 50 µm 400 m at 10G Building backbone, longer
Multimode OM5 50 µm 400 m at 10G, wideband New installs, SWDM
Single-mode OS2 9 µm 10 km+ Campus, ISP, long haul

The rule of thumb: multimode inside and between nearby buildings, single-mode for anything that might grow. If a new campus is 2 km away, single-mode is the only answer.

Optics

Form factor Speed Notes
SFP 1 Gbps Legacy access
SFP+ 10 Gbps Standard building uplink
SFP28 25 Gbps New core
QSFP+ / QSFP28 40/100 Gbps Core and aggregation

A copper DAC is cheaper for short runs inside a rack; an AOC (active optical cable) is lighter and longer. Both bypass the patch panel, which is fine for a rack and wrong for a building.

The optic must match the fiber, not just the speed

A 10GBASE-SR optic is multimode at 850 nm. A 10GBASE-LR is single-mode at 1310 nm. Plugging an LR into multimode gives a link that never comes up, and plugging SR into single-mode gives a link that works only if you are very lucky and very short.

Connectors and polish

Connector Use Notes
LC Standard for SFP Small form factor, duplex clip
SC Older patch panels Square, push-pull
ST Legacy Bayonet, being retired

Polish matters: UPC (blue) and APC (green, angled) do not mate. An APC connector into a UPC port produces high loss and sometimes damage. Match the color, not just the shape.

Polarity

A duplex fiber pair has transmit and receive. Three polarity schemes exist (A, B, C), and a mismatch produces a link where each side transmits into the other's transmitter.

The practical rule: pick one scheme, document it, and use the same patch cords throughout. A single straight-through cord in a crossover scheme breaks one link and wastes an hour.

Multimode inside, single-mode for distance, and three ways to get the pairing wrong.

Worked example: building to building

Two buildings 380 m apart, 10 Gbps required.

Option Feasible Notes
OM3 multimode No 300 m limit
OM4 multimode Yes 400 m limit, tight margin
OS2 single-mode Yes Plenty of margin, future 100G

The OM4 option works today and is at the edge of its budget. Single-mode costs more per optic and removes the distance question permanently. For a link that will outlive two switch generations, single-mode is usually the better decision.

What breaks in production

  • SR optic on single-mode (or the reverse), producing no link.
  • APC into UPC, producing high loss or damaged ferrules.
  • Polarity mismatch, where both ends transmit.
  • Dirty connectors, the single most common cause of intermittent fiber faults.
  • A bend tighter than the cable allows, producing loss that varies with temperature.

Checklist

  1. Fiber type and distance are documented for every run.
  2. Optic type matches the fiber (SR/OM, LR/OS2).
  3. Connector polish matches at both ends.
  4. One polarity scheme, documented and used consistently.
  5. Every connector is cleaned and inspected before mating.
  6. Spare optics and patch cords are stocked, matched to what is installed.